Biomass boilers are high-temperature and high-pressure thermal equipment, and are one of the special equipment widely used in government agencies, public institutions, and various industries. They are dangerous and special equipment. Once an accident occurs, involving public safety, it will cause huge losses to the lives and property of the country and the people. For the safety of public safety, people's lives, and property, according to the Regulations on the Safety Supervision of Special Equipment, the following precautions should be taken when using boilers:
1、 Precautions for the production, installation, and use of biomass boilers.
1. When the boiler leaves the factory, it should be accompanied by "design documents required by safety technical specifications, product quality certificates, safety and maintenance instructions, and supervision and inspection certificates (safety performance supervision and inspection certificates)".
2. Installation, maintenance, and renovation of boilers. Units engaged in boiler installation, maintenance, and renovation shall obtain a special equipment installation and maintenance qualification certificate issued by the provincial quality and technical supervision bureau before engaging in boiler installation, maintenance, and renovation. The construction unit shall inform the special equipment safety supervision and management department of the municipality or jurisdiction in writing of the proposed installation, maintenance, and renovation before construction, and submit the commencement notice to the local county-level quality and technical supervision bureau for filing. After notification, construction can begin.
3. Acceptance of boiler installation, maintenance, and renovation. After the construction is completed, the construction unit shall apply to the Special Equipment Inspection Institute of the Quality and Technical Supervision Bureau for the water pressure test and installation supervision inspection of the boiler. After passing the inspection, the Quality and Technical Supervision Bureau, Special Equipment Inspection Institute, and County Quality and Technical Supervision Bureau will participate in the overall acceptance.
4. Registration of boilers. After the boiler acceptance, the user must fill out the "Boiler (Survey) Registration Form" in accordance with the "Regulations on Registration and Use Management of Special Equipment", register with the Quality and Technical Supervision Bureau, and apply for the "Special Equipment Safety Use Registration Certificate".
5. Operation of the boiler. Boiler operation must be carried out by trained and qualified personnel who have obtained the "Special Equipment Operator Certificate". During use, the operating procedures, eight regulations, and six records must be strictly followed.
6. Boiler inspection. The boiler shall be inspected regularly once a year, and boilers that have not undergone regular safety inspections shall not be used. The safety accessories of the boiler, such as the safety valve, should be inspected regularly once a year, and the pressure gauge should be inspected every six months. Safety accessories that have not undergone regular inspections are not allowed to be used.
7. It is strictly prohibited to install atmospheric boilers as pressure boilers for use. It is strictly prohibited to use boilers with incomplete water level gauges, safety valves, and pressure gauges as the three major safety accessories

2、 Precautions for operating biomass atmospheric hot water boiler
1. Biomass atmospheric hot water boilers shall not be used under pressure, and the hot water temperature shall not exceed 90 ℃.
2. It is not allowed to install any valves, reduce the diameter, or block the atmospheric connecting pipes of biomass atmospheric hot water boilers.
3. Each unit in the system should be promptly vented.
When the system is short of water, it should be replenished in a timely manner.
5. The water quality of boiler water and make-up water should comply with the requirements of GB1576-2001 "Water Quality for Industrial Boilers"
Ding.