Mobile fire monitor electric PSKDY50ZB mobile fire monitor factory direct sales
Mobile fire monitor electric PSKDY50ZB mobile fire monitor factory direct sales

Mobile fire monitor electric PSKDY50ZB mobile fire monitor factory direct sales

Category:

Security/Firefighting equipment/Other fire-fighting equipment

Model:

PSKDY50ZB

Brand:

Eastern Mountain

Retail Price

12,000.00USD


重量

kg

  • Product Description
  • Description :

      1. There is a circle of 34 steel balls between the gun base and the gun body, which serve as a fixed and horizontal axis for rotation. Butter (lithium based lubricating oil) should be regularly injected from the "straight through oil injection cup" mouth; If 10 "butterfly lock nuts" are found missing or steel balls fall out, they should be promptly replenished and repaired. It is strictly prohibited to use them before repair to avoid accidents.

      2. Fixed fire monitor components should be kept intact. If loose or damaged fasteners are found, they should be repaired in a timely manner. Lubricating oil should be regularly added to all operating parts.

      3. If a fixed fire monitor is installed outdoors in a windy and sandy area, please purchase a gun cover or tarpaulin to cover it, in order to prevent blockage of the gun barrel and operational failure.

      4. Entering winter, fixed fire guns have been used. Please drain the remaining water from the gun body to prevent it from freezing and cracking.

      9、 Fault analysis and troubleshooting

      Fault phenomenon

      

      Root cause analysis

      

      treatment method

      

      Horizontal operation is not flexible

      

      Lack of lubricating grease

      

      Inject lubricating grease from the oil nozzle

      

      The pitch operation is not flexible

      

      O-ring damaged

      

      Replace O-ring

      

      Spray effect not achieved

      

      The water quality contains many impurities, which can block the muzzle of the cannon

      

      Remove the rotating body and connecting components, and remove any impurities from them.

      

      Water seepage at the connection point

      

      O-ring wear

      

      Replace the O-ring at the connection point

      

    AfterSalesService :

    Key words:
    • Mobile fire monitor