-40+120 degree smoke alarm, high and low temperature resistant industrial smoke detector
-40+120 degree smoke alarm, high and low temperature resistant industrial smoke detector

-40+120 degree smoke alarm, high and low temperature resistant industrial smoke detector

Category:

Security/Anti theft and alarm equipment/Other anti-theft and alarm equipment and systems

Model:

JTY-GD-HA801-G

Brand:

Hongsheng High Tech

model:

JTY-GD-HA801-G

Scope of Application:

indoor

power supply:

9-36

contact method:

wired

ambient temperature:

-40+80

Environmental humidity ≤:

ninety-five

Installation method:

ceiling-mounted

alarm method:

On site alarm/signal output

Overall dimensions:

104*51

manufacturer:

Hongsheng High Tech

Retail Price

258.00USD


重量

kg

  • Product Description
  • model

    JTY-GD-HA801-G

    Scope of Application

    indoor

    power supply

    9-36

    contact method

    wired

    ambient temperature

    -40+80

    Environmental humidity ≤

    ninety-five

    Installation method

    ceiling-mounted

    alarm method

    On site alarm/signal output

    Overall dimensions

    104*51

    manufacturer

    Hongsheng High Tech

    Description :

      Product Overview

      The networked photoelectric smoke and fire detector (hereinafter referred to as the detector) adopts a specially designed infrared photoelectric sensor, a reliable MCU, and SMT surface mount processing technology for production. It has the characteristics of high sensitivity, stability and reliability, low power consumption, beautiful and durable appearance, and easy use

      Performance Characteristics

      The detector adopts a specially designed photoelectric sensor combined with a reliable MCU, which can effectively detect the smoke generated during the initial smoldering stage or after the fire. When smoke enters the detector, it causes the light source to scatter, and the light receiving element senses the light intensity. The received light intensity has a certain linear relationship with the smoke concentration. The detector continuously collects, analyzes, and judges the on-site parameters. When it is confirmed that the light intensity of the on-site data reaches the predetermined threshold, the relay output is activated.

      When the smoke in the environment returns to normal, the detector automatically returns to normal working condition.

      Self check: Under normal circumstances, press the self check test button to perform internal functional testing on the detector and output the relay.

      Attention: When the detector alarms, the output relay has passive contacts with contact capacity 1A/24VDC

      Product Parameters

      Power supply: DC9V~DC46V

      Current: Static current ≤ 300uA

      Alarm current ≤ 45mA

      Working temperature: -40 ℃ to+120 ℃

      Relative humidity: ≤ 97% RH (40 ℃± 2 ℃)

      Output form: The relay contacts are normally closed at the factory, with a contact capacity of 1A/24VDC,

      Working environment: resistant to strong magnetic interference

      Smoke sensitivity: 0.15-0.3dB/

      Dimensions: 79 * 59 * 26

    AfterSalesService :

    Key words:
    • smoke alarm