Single and double cabinet heptafluoropropane gas fire extinguishing device

Single and double cabinet heptafluoropropane gas fire extinguishing device

Category:

Security/Firefighting equipment/Fire extinguishing equipment

Model:

GQQ100/2.5

Brand:

Zhengsheng Fire Protection

Retail Price

10,000,000.00USD


重量

kg

  • Product Description
  • Description :


    1、 Product Introduction

    GQQ cabinet heptafluoropropane belongs toPrefabricated fully submerged clean gas fire extinguishing equipment without pipeline network (national standard GB16670)The entire set of steel cylinders, valves, pipelines, and nozzles are integrated inside the steel cabinet and placed directly on the ground in the protective area,No need to build a separate gas cylinder room, no need to embed a large area of pipeline network, DC24V electronic control perfectly matches the Dingxin fire alarm controller, with automatic linkage start stop, making it the mainstream choice for medium and large distribution rooms and chemical instrument rooms.


    The fire extinguishing agent HFC-227ea has clean insulation, low toxicity and no residue, with an ODP of 0 and does not damage the ozone layer. The fire extinguishing relies on the dual effects of chemical chain breaking and physical cooling, and can quickly extinguish the fire in a room with a spraying time of ≤ 8 seconds. It can be used in compliance with regulations in rooms where someone is on duty.


    2、 System composition

    Cabinet+heptafluoropropane storage bottle+container valve+DC24V electromagnetic starter+signal feedback device+high-pressure hose+top mounted atomizing nozzle+pressure gauge, safety relief components;

    Three startup modes: automatic linkage, on-site mechanical manual, remote electronic control manualAfter a fire alarm, a 30 second personnel evacuation delay is reserved, and the spraying signal is simultaneously fed back to the Dingxin host.


    3、 Mainstream commonly used specifications (2.5MPa storage pressure)

    table


    modelBottle volumePharmaceutical filling amountMaximum protection capacity per unitApplicable Scenarios
    GQQ70/2.570L77kg115m³Small and medium-sized distribution rooms, instrument rooms
    GQQ100/2.5100L110kg165m³UPS machine room, laboratory
    GQQ120/2.5120L132kg200m³Coal chemical electrical control auxiliary room
    Double bottle 120L120L×2264kg400m³Large and medium-sized data centers
    Note: A maximum of 10 cabinet machines can be connected in parallel in a single protection zone, with a maximum protection capacity of 1600m ³.